File ⇒ CAN - data logging…
perform the settings on the controller
For data logging using the UVR1611 via a CAN bus, two data records can be defined with the parameters to be captured. One data record comprises 16 analogue and 13 digital parameters, which can be freely defined. The left column shows all the parameters available for data logging. These can be added to the selected data record in the right column. In this respect the following details must be observed:
To capture the speed stage of an output, the digital parameter with the same number must be allocated to the output in data record 1. The output A6 must be allocated to parameter DIGITAL 6. If the output is allocated to another parameter, then status output still occurs (ON/OFF), but no speed stage output.
The output variables of the „heat quantity counter“ functions are, according to the sequence in the function list (see „ordering functions“), automatically linked by the UVR1611 to the two data records (heat quantity counters 1 and 2 in data record 1, heat quantity counters 3 and 4 in data record 2). The parameters of a „heat quantity counter“ function are therefore also not displayed in the list of available parameters.
(for further clarification, see the diagram on the next page)
as well as the keyboard shortcut Ctrl + right arrow key insert the parameter selected in the <available parameters> list in the selected position in the data record. The cursor is then automatically placed in the next position in the data record.
as well as the button Del remove the parameter highlighted in the data record. The cursor is then automatically placed in the next position in the data record.
Deletes all parameters in the selected data record.
Loads the default settings for the selected data record.
Basic, global settings for the CAN network (device node number, enable, etc.). These settings can also be set when parameterizing the network inputs and network outputs.